Construction

These settings describe how the building's external walls, roof, internal walls and ground-floor slab pass heat, and whether radiant heat is released with a delay. They apply to every room in the calculation; the area and orientation of each wall come from the drawing, and the heat-transfer coefficients of external walls, roof and glass come from the building and room settings.

Construction

Radiant time delay

On screen: Radiant time delay (Yes or No).

Part of every heat gain is radiant. It warms the room's surfaces first and reaches the air in the following hours. The tick decides whether the calculation allows for that.

Setting Meaning
On (default) The radiant share of each gain is released over the following hours.
Off Every gain is load in its own hour.

Lighting is always taken as a recessed LED troffer with a uniform diffuser, whose radiant share is 37 %.

How the share is worked out: see Time delay of radiant gains.

Q = (1 − r) × q(h) + r × Σn RTFn × q(h − n)

Construction

On screen: Construction (shown only while Radiant time delay is Yes).

How much heavy material the building has. It sets how long the walls, floor and furniture hold radiant heat before giving it to the air. One class applies to the whole building. Light, Medium and Heavy are the three descriptions of the industry standard:

Choice What the room is made of Effect on the load
Light Steel siding on the walls; 100 mm lightweight concrete floor Little heat is stored, so radiant heat reaches the air quickly. The peak is higher and earlier.
Medium (default) 100 mm face brick walls; 100 mm concrete floor Suits most brick or block offices with concrete slabs.
Heavy Face brick with 200 mm concrete in the walls; 200 mm concrete floor A lot of heat is stored and returned slowly. The peak is lower and later.

If you are unsure, leave it on Medium. Carpet on the floor, ticked per floor under Floor finish in Floor settings, changes the delay further: carpet returns the heat sooner, because the slab underneath stores less. The Explain screen names the class used.

See Time delay of radiant gains.

Partition ΔT

On screen: Partition ΔT (partition ΔT reduction).

How much cooler the space behind an internal wall that faces unconditioned space is assumed to be than outdoors, as a percentage of the outdoor-minus-indoor temperature difference. A partition facing an air-conditioned room carries no load at all, whatever this value.

Setting Value
Default 25 %
Allowed 0 to 100 %, in steps of 5

The hover text on the screen gives an example: 34 °C outside, 24 °C inside, 25 % less, so the space behind is taken as 31.5 °C.

reduction = setting ÷ 100

Internal doors and windows count as part of the wall face. The interior face is charged only over the length that faces unconditioned space — a stretch facing an air-conditioned room carries nothing — at U of the wall's Interior wall type:

Qpartition = Σ Uinterior × Acharged × (Toutdoor − Tindoor) × (1 − reduction)

The setting applies only to walls facing unconditioned space: a stretch facing an air-conditioned room already carries nothing. The default suits a wall to a corridor or store that is not cooled but is shaded from the weather. Lower it towards 0 % when the spaces behind are hot, such as plant rooms. The same value applies to every charged internal wall in the calculation.

See Glass, partitions and the ground slab.

Ground ΔT

On screen: Ground ΔT (ground ΔT reduction).

The same idea applied to the floor slab of ground-floor rooms: how much cooler the ground is assumed to be than the outdoor air, as a percentage of the outdoor-minus-indoor difference. 100 % removes the floor load.

Setting Value
Default 25 %
Allowed 0 to 100 %, in steps of 5

The hover text gives an example: 34 °C outside and 24 °C inside with 25 % less puts the ground at 31.5 °C. It applies in winter as well: 5 °C outside and 21 °C inside gives 9 °C.

Qslab = U × Afloor × (Toutdoor − Tindoor) × (1 − reduction) (ground floor only)

See Glass, partitions and the ground slab.

How layers, absorptance, glazing and shading enter the load

The settings above are shared by every room. The construction of each surface comes from its preset, and the industry-standard formulas turn those presets into an hour-by-hour load (the basis is described on Calculation method):

Open a room's working from the results table to see each of these as a line with its value and its source chapter.